Inspection Cabinet GT-XJ

Product Detail

Inspection Cabinet GT-XJ | Product Overview

Operating Environment

  • Ambient temperature: -10°C to +40°C
  • Ambient humidity: 0% to 90% with no condensation
  • Altitude: Less than 1000 meters

Scope of Use

  1. Using a variable-frequency drive (VFD) to control the inspection pump results in a lower starting current and reduced pump speed, thereby minimizing mechanical impact on the pump and extending its service life — particularly significant for high-power pumps.
  2. The variable-frequency inspection drive consumes low power and operates with high efficiency and energy savings, requiring only approximately 1.35% of the power required by the industrial-frequency inspection system, significantly conserving electrical resources.
  3. The fire inspection cabinet automatically conducts inspections at preset intervals without manual operation. Equipped with multiple communication interfaces, it enables remote fire monitoring, allowing real-time monitoring of the status of fire pump units for efficient management. The system features user-friendly operation, intuitive interface, stable performance, and high reliability.
  4. It features fault alarms, facilitating maintenance personnel in inspection and fault analysis.
  5. During the inspection, if a fire alarm signal is detected, immediately cease the inspection and activate both the fire hydrant pump and the sprinkler pump.
  6. The fire inspection cabinet features convenient wiring and is compatible with control cabinets manufactured by any switchgear manufacturer.

Product Features

  • Main models: 110KW, 75KW, 37KW, 22KW, 15KW
  • Model variants: GT-XJ-A, GT-XJ-B, GT-XJ-C, GT-XJ-D, GT-XJ-E

Model & Applicable Scenarios

This system is widely applicable in residential communities, production bases, office buildings, shopping malls, hotels, schools, warehouses, hospitals, military installations, and other similar venues. It is also suitable for retrofitting existing fire protection systems, enabling efficient utilization of original fire safety infrastructure to reduce operational costs for users.

Implementation standard: GB 16806-2006

Inspection Cabinet Functions

  • Operation Mode: Bring your own / Custom made
  • You can set an automatic inspection for any time period.
  • The inspection of the main circuit switching components should not exceed 2 seconds.
  • Perform inspection unit by unit in low-speed, low-frequency, and pressure-free mode.
  • Network pipeline protection function, pressure-resistant inspection function.
  • Exit inspection upon receiving a fire alarm and immediately switch to operational mode.
  • Smart Alarm Function
  • Audio and visual alarm function.
  • Fault storage recording function.
  • It features protection functions such as overvoltage, overcurrent, short circuit, and phase loss.
  • Test unit function.
  • Water level monitoring and pipeline pressure alarm function for the pool.
  • Featuring 485 communication functionality and compatibility with fire protection system networking.